Properties:
GT-604 is built with organophosphoric acid, polycarboxylic acid, carbon iron and copper corrosion inhibitor. GT-604 can effectively chelate and disperse calcium carbonate, calcium sulfate and calcium phosphate scales. GT-604 has good scale inhibition effect on steel & iron and copper. GT-604 is mainly used in circulating cool water system in power plant, chemical plant, petrochemical, steel & iron. It has the advantages of effective and strong corrosion inhibition.
Specification:
project | index |
Appearance | Brown transparent liquid |
Thiazole(C6H5N3)% | 1.0 min |
Total phosphoric acid (as PO43-)% | 20 max |
Phosphorous acid(as PO33-)% | 1.0 max |
phosphoric acid (as PO43-)% | 0.5 max |
Solid content % | 32.0 min |
PH(1% water solution) | 3.0±1.5 |
Density 20℃(g/cm3) | 1.15 min |
Usage:
Add GT-604 into plastic pool (or box) every day, dilute with water and continuously add into inlet of dosage pump or metering valve (outlet of collecting tank). Dosage of 5-20ppm is preferred (according to quantity of makeup water).
Package and Storage:
200L plastic drum,IBC(1000L),customers’ requirement. Storage for one year in shady room and dry place.
Safety Protection:
Acidity, Avoid contact with eye and skin, once contacted, flush with water.